Nigerian Recline Cables

Manufacturer, factory, supplier, company from China 16mm 25mm 35mm 50mm 70mm recline cable price Overhead Aluminium conductor Aerial Bounded Cable Recline cable MOQ: 5KM Send e-mail for price list

Telephone:+86-13523009770

Product Introduction

Brief introduction

The Insulated Aerial cable is made up of the aluminium (aluminium alloy) conductor, inner shield, climate-resistant insulation material and outer shield. It has structure and is safe a nd reliable. It has both excellent properties of the power cable and good physical properties of the aerial cable. By using the climate-resistant insulation material, the product has the excellent properties of resistance to air aging. Compare with the bare wire, it has good characteristics such as smaller laying distance, higher reliability. Itissuitableforusing in the high buildings, brushland and bad weather zone.

Structure

Number of cores x 

nominal cross section

max. conductor- resistance

min. breaking load 

of conductor strand

Current rating in the air

Outer diameter

Total weight

mm^2

Ohm/km

kN

A

mm

kg/km

4x 16 RM

1,910

2,5

72

188

286

4x 25 RM

1,200

4,0

107

212

430

4x 35 RM

0,868

5,5

132

241

553

4x 50 RM

0,641

8,0

165

278

746

4x 70 RM

0,443

10,7

205

318

1009

4x 95 RM

0,320

13,7

240

378

1332

4x 120 RM

0,253

18,6

290

544

1632

4x 50 + 1x 25 RM

0,641/1,200

8,0/4,0

165/107

319

814

4x 50 + 1x 35 RM

0,641/0,868

8,5/5,5

165/132

319

845

4x 70 + 1x 25 RM

0,443/1,200

10,7/4,0

205/107

360

1105

4x 70 + 2x 25 RM

0,443/1,200

10,7/4,0

205/107

400

1217

4x 95 + 1x 25 RM

0,320/1,200

13,7/4,0

240/107

418

1438

4x 95 + 2x 25 RM

0,320/1,200

13,7/4,0

240/107

420

1544

4x120 + 1x 25 RM

0,253/1,200

18,6/4,0

290/107

590

2050

 

Construction

Conductor (for either phase, neutral or street lighting)

The conductors shall be of aluminium 1350 wires and are compacted circular stranded(RM).

Insulation

XLPE/PE as requirements

Assembly

2 up to 4 cores of equal cross section are stranded together in left-hand lay, additionally 1 or 2 cores of reduced cross section can be co-stranded.

Technical Data

Rated voltage

kV

0.6/1

Test voltage

Veff kV

4

Laying temperature

°C

min. -20

Operating temperature

°C

-30 ~ +80

Conductor temperature

°C

max. +80

Short-circuit temperature

°C/s

max. +130 /5

Bending radius (min.)

 

18 × o of cable

Key words:

Nigerian Recline Cables

Related Products

Product inquiry

Note: Please leave your contact information and our professionals will contact you as soon as possible!