Aluminum Conductor 15kV 25KV 28KV 35KV Primary URD EPR Concentric Cable

Aluminum or Copper Conductor. EPR Insulation. Bare Copper Concentric Neutrals. Low Density Polyethylene Jacket.

Telephone:+86-13523009770

Product Introduction

APPLICATIONS

Predominantly used for primary underground distribution in conduit systems; suitable for use in wet or dry locations, direct

burial, underground duct, and where exposed to sunlight. To be used at 15,000 volts or less and at conductor

temperatures not to exceed 105°C for normal operation.

SPECIFICATIONS

15kV Primary UD EPR Cable meets or exceeds the following ASTM specifications:

• B3 Soft Annealed Copper Wire

• B8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft

• B230 Aluminum, 1350-H19 Wire for Electrical Purposes

• B231 Aluminum 1350 Conductors, Concentric-Lay-Stranded

• B609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes

• ANSI/ICEA S-94-649

• AEIC CS-8

• UL 1072, When Specified

• RUS 1728F-U1

• ANSI/ICEA S-94-649

• AEIC CS-8

• UL 1072, When Specified

• RUS 1728F-U1

CONSTRUCTION

The cable is composed of a solid or moisture blocked reverse lay, compressed stranded soft drawn copper, or a solid or

moisture blocked reverse lay or unilay compressed stranded 1350-H16/26 aluminum phase conductor, covered by a

semi-conducting cross-linked polyethylene strand shield, an ethylene propylene rubber primary insulation, and a semiconducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation

levels. A concentric neutral of bare copper wires and a sunlight resistant, -40°C rated, insulating linear low density

polyethylene jacket are applied over the insulation shield. The cable is identified by surface print on the jacket and with the

lightning bolt symbol for supply cables indented in the jacket. Red extruded stripes available upon request. A semiconducting polyethylene jacket is also available upon request.

Phase Conductor

 Neutral

 Thickness Per Cond. (mils)

Diameter (mils)

Weight 1000 feet (lbs.)

Allowable Ampacities+

Size (AWG or kcmil)

 

Strand- ing

 

No. of Wires

 

Size (AWG)

 

Nominal Insul.

Insul. Shield min. Point

 

Approx. Jkt.

Bare Phase Cond.

 

Over Insul.

Over Insul. Shield

 

Comp. Cable

 

Comp. Cable

 

Direct Burial

 

In Ducts

ALUMINUM CONDUCTOR - 100% INSULATION LEVEL

2

Solid

10

14

175

30

50

258

653

733

961

485

168*

119*

2

7

10

14

175

30

50

283

678

758

986

504

168*

119*

1

Solid

13

14

175

30

50

289

685

765

993

555

193*

137*

1

19

13

14

175

30

50

322

718

798

1026

577

193*

137*

1/0

Solid

16

14

175

30

50

325

720

800

1028

629

218*

155*

1/0

19

16

14

175

30

50

352

748

828

1056

648

218*

155*

2/0

19

20

14

175

30

50

395

790

870

1098

745

248*

177*

3/0

19

25

14

175

30

50

443

838

918

1146

862

284*

201*

4/0

19

20

12

175

30

50

498

893

973

1234

1042

324*

230*

250

37

16

10

175

30

50

558

963

1043

1346

1268

360*

257*

350

37

18

14

175

40

50

661

1068

1168

1396

1118

389**

319**

500

37

25

14

175

40

50

789

1193

1293

1521

1419

468**

384**

750

61

24

12

175

40

80

968

1383

1483

1798

2030

569**

468**

1000

61

20

10

175

40

80

1117

1530

1630

1988

2567

642**

542**

1250

91

25

10

220

55

80

1250

1765

1895

2253

3278

688**

604**

1500

91

30

10

220

55

80

1370

1885

2015

2373

3762

726**

637**

COPPER CONDUCTOR - 100% INSULATION LEVEL

2

Solid

16

14

175

30

50

258

653

733

961

697

210*

150*

2

7

16

14

175

30

50

283

678

758

986

719

210*

150*

1

Solid

20

14

175

30

50

289

685

765

993

815

240*

171*

1

19

20

14

175

30

50

322

718

798

1026

841

240*

171*

1/0

Solid

25

14

175

30

50

325

720

800

1028

959

273*

194*

1/0

19

25

14

175

30

50

362

758

838

1066

991

273*

194*

2/0

19

20

12

175

30

50

405

800

880

1142

1204

313*

224*

3/0

19

25

12

175

30

50

456

853

933

1194

1437

358*

255*

4/0

19

20

10

175

30

50

512

908

988

1291

1768

410*

293*

250

37

24

10

175

30

50

558

963

1043

1346

2047

446*

322*

350

37

18

12

175

40

50

661

1068

1168

1429

2027

489**

400**

500

37

26

12

175

40

50

789

1193

1293

1554

2722

577**

472**

750

61

25

10

175

40

80

968

1383

1483

1840

3990

649**

532**

1000

61

26

9

175

40

80

1117

1530

1630

2013

5136

720**

630**

1250

91

26

8

220

55

80

1250

1765

1895

2306

6535

760**

667**

+ Ampacities shown assume use of 100% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C

conductor temperature, earth RHO 90, insulation and shield RHO 400

* Full neutral construction (Ampacities assume - single phase circuit, one cable)

** 1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods)

 

 

Phase Conductor

 

Neutral

Thickness Per Cond. (mils)

Nominal Diameter (mils)

Weight 1000 feet (lbs.)

Allowable Ampacities+

 

Size (AWG or kcmil)

 

Strand- ing

 

No. of Wires

 

Size (AWG)

 

Nominal Insul.

Insul. Shield min. Point

 

Approx. Jkt.

 

Bare Phase Cond.

 

Over Insul.

 

Over Insul. Shield

 

Comp. Cable

 

Comp. Cable

 

Direct Burial

 

In Ducts

ALUMINUM CONDUCTOR - 0.220" INSULATION - 133% INSULATION LEVEL

2

Solid

10

14

220

30

50

258

745

825

1053

556

168*

119*

2

7

10

14

220

30

50

283

770

850

1078

577

168*

119*

1

Solid

13

14

220

30

50

289

778

858

1086

628

193*

137*

1

19

13

14

220

30

50

322

810

890

1118

652

193*

137*

1/0

Solid

16

14

220

30

50

325

813

893

1121

705

218*

155*

1/0

19

16

14

220

30

50

352

840

920

1148

726

218*

155*

2/0

19

20

14

220

30

50

395

883

963

1191

826

248*

177*

3/0

19

25

14

220

30

50

443

930

1010

1238

947

284*

201*

4/0

19

20

12

220

30

50

498

985

1065

1327

1133

324*

230*

250

37

16

10

220

40

50

558

1055

1155

1459

1389

360*

257*

350

37

18

14

220

40

50

661

1158

1258

1486

1219

389**

319**

500

37

25

14

220

40

50

789

1285

1385

1613

1532

468**

384**

750

61

24

12

220

40

80

968

1475

1575

1891

2162

569**

468**

1000

61

20

10

220

55

80

1117

1623

1753

2110

2762

642**

542**

1250

91

25

10

220

55

80

1250

1765

1895

2253

3278

688**

604**

1500

91

30

10

220

55

80

1370

1885

2015

2373

3762

726**

637**

COPPER CONDUCTOR - 0.220" INSULATION - 133% INSULATION LEVEL

2

Solid

16

14

220

30

50

258

745

825

1053

768

210*

150*

2

7

16

14

220

30

50

283

770

850

1078

792

210*

150*

1

Solid

20

14

220

30

50

289

778

858

1086

888

240*

171*

1

19

20

14

220

30

50

322

810

890

1118

916

240*

171*

1/0

Solid

25

14

220

30

50

325

813

893

1121

1035

273*

194*

1/0

19

25

14

220

30

50

362

850

930

1158

1070

273*

194*

2/0

19

20

12

220

30

50

405

893

973

1234

1288

313*

224*

3/0

19

25

12

220

30

50

456

943

1023

1284

1523

358*

255*

4/0

19

20

10

220

30

50

512

1000

1080

1384

1863

410*

293*

250

37

24

10

220

40

50

558

1055

1155

1459

2168

446*

322*

350

37

18

12

220

40

50

661

1158

1258

1519

2130

489**

400**

500

37

26

12

220

40

50

789

1285

1385

1647

2837

577**

472**

750

61

25

10

220

40

80

968

1475

1575

1933

4125

649**

532**

1000

61

26

9

220

55

80

1117

1623

1753

2135

5332

720**

630**

1250

91

26

8

220

55

80

1250

1765

1895

2306

6535

760**

667**

+ Ampacities shown assume use of 100% load factor, 60 Hz current, 36" burial depth, 20°C ambient temperature, 90°C conductor temperature, earth RHO 90, insulation and shield RHO 400

* Full neutral construction (Ampacities assume - single phase circuit, one cable

** 1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods)

Key words:

Aluminum Conductor 15kV 25KV 28KV 35KV Primary URD EPR Concentric

Related Products

Product inquiry

Note: Please leave your contact information and our professionals will contact you as soon as possible!