AAAC Overhead Conductor

All Aluminum Alloy Conductor (AAAC) Bare Conductor for high voltage transmission line Send the details by email for price list now

Classification:

Telephone:+86-13523009770

Product Introduction

Application

AAAC-Aluminum Alloy Overhead Bare Conductor is mainly used as bare overhead transmission cable and as primary and secondary distribution cable. It is also suitable for laying across basins, rivers and valleys where special geographical teatures exist.

Construction

AAAC Aluminum Alloy Overhead Bare Conductor cable consists of aluminum alloy wires concentrically stranded.

Advantage:

1. Corrosion Resistance: AAAC exhibits excellent corrosion resistance specially in sea coast areas and in polluted industrial areas due to absence of steel core.

2. Lower Power losses: Since AAAC is homogeneous (with all strands of Aluminium Alloy) with no steel component the resistance of AAAC is lower as compared to ACSR.

3. Higher Ampacity: AAAC can carry atleast 15-20% extra current as compared to ACSR of equal size

Longer Life: Experience in foreign countries shows that All Aluminium Alloy Conductors are in service for over 60 years, which is about double the life of ACSR Conductors.

AAAC Standard

AAAC 6201

Code Word

 

 

Conductor size

Size and stranding of ACSR

equivalent

 

 

 

Wires

 

 

Wire diameter

 

Cable diameter

 

 

Mass

 

 

Rated strength

Nominal d.c.

Ampacity

 

Resistance at 20 °C

Sun, no wind

Sun and wind

No sun and wind

kcmil

mm²

AWG or kcmil

mm

mils

mm

in

kg/km

lb/kft

kgf

kips

W/ km

W/kft

A*

Akron

30,58

15,5

6

7

1,68

66,1

5,04

0,198

42,5

28,6

502

1,107

2,161

0,6588

62

107

111

Alton

48,69

24,7

4

7

2,12

83,4

6,36

0,25

67,7

45,5

799

1,762

1,358

0,4138

85

143

150

Ames

77,47

39,2

2

7

2,67

105,2

8,02

0,316

107,7

72,4

1272

2,804

0,853

0,2601

119

191

201

Azusa

123,3

62,4

1/0

7

3,37

132,7

10,1

0,398

171,4

115,2

1939

4,275

0,536

0,1635

164

256

271

Anaheim

155,4

78,6

2/0

7

3,78

149

11,4

0,447

216,1

145,2

2445

5,390

0,425

0,1297

192

296

315

Amherst

195,7

99,3

3/0

7

4,25

167,2

12,7

0,502

272,1

182,8

3079

6,787

0,338

0,1030

226

342

365

Alliance

246,9

125

4/0

7

4,77

187,8

14,3

0,563

343,2

230,7

3884

8,563

0,268

0,0816

265

395

424

Butte

312,8

159

266,8

19

3,26

128,3

16,3

0,642

434,8

292,2

4767

10,508

0,211

0,0644

313

460

495

Canton

394,5

200

336,4

19

3,66

144,1

18,3

0,721

548,5

368,6

6013

13,256

0,168

0,0511

368

532

575

Cairo

465,4

236

397,5

19

3,98

156,5

19,9

0,783

647

434,8

7092

15,636

0,142

0,0433

413

590

640

Darien

559,5

284

477

19

4,36

171,6

21,8

0,858

777,9

522,8

8527

18,798

0,118

0,0360

468

663

720

Elgin

652,4

331

556,5

19

4,71

185,3

23,5

0,927

907

609,6

9943

21,920

0,101

0,0309

520

729

795

Flint

740,8

375

636

37

3,59

141,5

25,2

0,991

1030

692,2

11048

24,356

0,089

0,0272

566

790

863

Greeley

927,2

470

795

37

4,02

158,3

28,1

1,11

1289

866,3

13827

30,483

0,071

0,0217

660

908

996

-

1077,4

547

954

61

3,38

132,9

30,4

1,2

1498

1007

15891

35,032

0,061

0,0187

733

998

1099

-

1165,1

590

1033,5

61

3,51

138,2

31,6

1,24

1620

1089

17183

37,882

0,057

0,0173

771

1045

1153

-

1259,6

638

1113

61

3,65

143,7

32,8

1,29

1751

1177

18578

40,958

0,052

0,0160

812

1096

1211

-

1348,8

685

1192,5

61

3,78

148,7

34

1,34

1875

1260

19894

43,857

0,049

0,0149

850

1143

1265

-

1439,2

729

1272

61

3,9

153,6

35,1

1,38

2001

1345

21226

46,795

0,046

0,0140

886

1187

1315

* Capacidad de corriente de conductores desnudos al aire libre, con base en temperatura ambiente de 25 °C, temperatura en el conductor 75 °C, velocidad del viento 0,6 m/s, emisividad del conductor 0,5, radiación solar 1000 W/m2 a nivel del mar.

* Allowed ampacities of bare conductors in free air, based on ambient temperature of 25 ºC, conductor temperature of 75 ºC, wind velocity 2 ft/s, conductor emisivity 0,5, solar radiation 96 W/ft2, at sea level.

Type AAAC 1120 – All Aluminium Alloy Conductor AS 1531-1991

Part

Number

Conductor Code

Stranding andWire

Diameter (No/mm)

Nominal

Overall

Diameter

(mm)

Cross

Sectional

Area

(mm2)

Approx.

Mass

(kg/km)

Breaking

Load

(kN)

Modulus

of

Elasticity

(GPa)

Coefficient of Linear 

 Expansion (x10-6/oC

DC

Resistance

(Ω/km)

AAAC/1120 - 7/2.50

Chlorine

7/2.50

7.5

34.36

94.3

8.18

65

23

0.864

AAAC/1120 - 7/2.75

Chromium

7/2.75

8.25

41.58

113

9.91

65

23

0.713

AAAC/1120 - 7/3.00

Fluorine

7/3.00

9

49.48

135

11.8

65

23

0.599

AAAC/1120 - 7/3.75

Helium

7/3.75

11.3

77.28

211

17.6

65

23

0.383

AAAC/1120 - 7/4.50

Hydrogen

7/4.50

13.5

111.3

304

24.3

65

23

0.266

AAAC/1120 - 7/4.75

Iodine

7/4.75

14.3

124

339

27.1

65

23

0.239

AAAC/1120 - 19/3.25

Krypton

19/3.25

16.3

157.6

433

37.4

65

23

0.189

AAAC/1120 - 19/3.50

Lutetium

19/3.50

17.5

182.8

503

41.7

65

23

0.163

AAAC/1120 - 19/3.75

Neon

19/3.75

18.8

209.8

576

47.8

65

23

0.142

AAAC/1120 - 37/3.00

Nitrogen

37/3.00

21

261.6

721

62.2

64

23

0.114

AAAC/1120 - 37/3.25

Nobelium

37/3.25

22.8

307

845

72.8

64

23

0.0973

AAAC/1120 - 19/4.75

Oxygen

19/4.75

23.8

336.7

924

73.6

65

23

0.0884

AAAC/1120 - 37/3.75

Phosphorus

37/3.75

26.3

408.5

1120

93.1

64

23

0.0731

AAAC/1120 - 61/3.25

Selenium

61/3.25

29.3

506.1

1400

114

64

23

0.0592

AAAC/1120 - 61/3.50

Silicon

61/3.50

31.5

586.9

1620

127

64

23

0.0511

AAAC/1120 - 61/3.75

Sulphur

61/3.75

33.8

673.4

1860

145

64

23

0.0444

AAAC conductor-DIN 48201 Part 6

Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
Nominal Teorical
mm^2 mm^2 No.xmm mm kg/km KN Ω/Km A
16 15.89 7/1.70 5.1 43 4.44 2.0742 78
25 24.25 7/2.10 6.3 66 6.77 1.3593 102
35 34.36 7/2.50 7.5 94 9.6 0.9591 126
50 49.48 7/3.00 9 135 13.82 0.666 158
50 48.35 19/1.80 9 133 13.5 0.6849 156
70 65.81 19/2.10 10.5 181 18.38 0.5032 189
95 93.27 19/2.50 12.5 256 26.05 0.3551 234
120 116.99 19/2.80 14 322 32.68 0.2831 269
150 147.11 37/2.25 15.8 406 41.09 0.2256 309
185 181.62 37/2.50 17.5 500 50.73 0.1828 352
240 242.54 61/2.25 20.3 670 67.74 0.1371 420
300 299.43 61/2.50 22.5 827 83.63 0.111 477
400 400.14 61/2.89 26 1104 111.76 0.0831 568
500 499.83 61/3.23 29.1 1379 139.6 0.0665 649
625* 626.2 91/2.96 32.6 1732 174.9 0.0531 742
800* 802.09 91/3.35 36.9 2218 224.02 0.0415 857
1000* 999.71 91/3.74 41.1 2767 279.22 0.0333 971

Get a free quote by e-mail: info@qingzhou-cable.com

AAAC conductor-ASTM B 399B 399M

Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
AWG&MCM mm^2 No.xmm mm kg/km KN Ω/Km A
6 13.2 7/1.55 4.65 36.2 4.18 2.5361 69
4 21.1 7/1.96 5.88 57.9 6.69 1.586 93
2 33.5 7/2.47 7.41 92 10.6 0.9987 123
0 53.5 7/3.12 9.36 146.8 17 0.62592 165
2/0 67.3 7/3.50 10.5 184.8 20.4 0.49738 190
3/0 84.9 7/3.93 11.79 233 25.7 0.3945 219
4/0 107 7/4.42 13.26 294.7 32.5 0.31188 253
250 126 19/2.91 14.55 346.7 38.8 0.26509 280
300 152 19/3.19 15.95 416.7 46.6 0.22059 313
350 178 19/3.45 17.25 487.3 52 0.1886 345
400 203 19/3.69 18.45 557.5 59.5 0.16486 375
450 228 19/3.91 19.55 626 66.8 0.14683 402
500 253 19/4.12 20.6 695 74.2 0.13224 429
550 279 37/3.10 21.7 766.2 83.9 0.11995 455
600 303 37/3.23 22.61 831.9 91 0.11049 478
650 330 37/3.37 23.59 905.5 94.9 0.1015 504
700 354 37/3.49 24.43 971.2 101 0.09464 525
750 381 37/3.62 25.34 1045 109 0.08796 549
800 404 37/3.73 26.11 1109 116 0.08285 569
900 456 37/3.96 27.72 1250 131 0.07351 612
1000 508 37/4.18 29.26 1393 146 0.06597 653
1250 631 61/3.63 32.67 1732 179 0.05306 743
1500 759 61/3.98 35.82 2082 215 0.04414 827
1750 886 61/4.30 38.7 2431 251 0.03781 904

Get a free quote by e-mail:info@qingzhou-cable.com

AAAC conductor-BS 3242

Code AL Nominal Area Cu Nominal Area Equivalent Total Area Stranding Overall Diameter Weight
  mm^2 mm^2 mm^2 No.Ω/mm mm kg/km
- - 6.45 11.7 7/1.47 4.41 32.2
Box - 9.68 18.8 7/1.85 5.55 51.7
Acacia - 12.9 21.9 7/2.08 6.24 66.1
Almond 25 16.1 30.1 7/2.34 7.02 82.9
Ceda 30 19.4 35.5 7/2.54 7.62 97.8
- 40 22.6 42.2 7/2.77 8.31 116.4
Fir 50 25.8 47.8 7/2.95 8.85 131.8
Hazel 100 32.3 59.9 7/3.30 9.9 165
Pine - 38.7 71.7 7/3.61 10.83 197.7
- - 45.2 84.1 7/3.91 11.73 231.6
Willow 150 48.4 89.8 7/4.04 12.12 247.5
- 175 51.6 96.5 7/4.19 12.57 266.2
- 300 58.1 108.8 7/4.45 13.35 299.8
Oak - 64.5 118.9 7/4.65 13.95 327.8
- - 80.6 118.8 19/2.82 14.1 327.6
Mulberry - 96.8 151.1 19/3.18 15.9 416.7
Ash - 113 180.7 19/3.48 17.4 498.1
Elm - 129 211 19/3.76 18.8 582.1
Poplar - 145 239 37/2.87 20.09 658.8
- - 161 270.8 37/3.05 21.35 746.7
Sycamore - 194 303 37/3.23 22.61 834.9
Upas - 226 362.1 37/3.53 24.71 998.6
- - 258 421.8 37/3.81 26.47 1163
Yew - - 479.9 37/4.06 28.42 132

AAAC conductor-BS EN 50182

Code Stranding Nominal Area Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
No.xmm mm^2 mm kg/km KN Ω/Km A
Box 7/1.85 18.8 5.55 51.4 5.55 1.748 87
Acacia 7/2.08 23.8 6.24 64.9 7.02 1.3828 101
Almond 7/2.34 30.1 7.02 82.2 8.88 1.0926 116
Cedar 7/2.54 35.5 7.62 96.8 10.46 0.9273 129
Deodar 7/2.77 42.2 8.31 115.2 12.44 0.7797 143
Fir 7/2.95 47.8 8.85 130.6 14.11 0.6875 155
Hazel 7/3.30 59.9 9.9 163.4 17.66 0.5494 178
Pine 7/3.61 71.6 10.83 195.6 21.14 0.4591 199
Holly 7/3.91 84.1 11.73 229.5 24.79 0.3913 219
Willow 7/4.04 89.7 12.12 245 26.47 0.3665 228
Oak 7/4.65 118.9 13.95 324.5 35.07 0.2767 272
Mulberry 19/3.18 150.9 15.9 414.3 44.52 0.2192 314
Ash 19/3.48 180.7 17.4 496.1 53.31 0.183 351
Elm 19/3.76 211 18.8 579.2 62.24 0.1568 386
Poplar 37/2.87 239.4 20.09 659.4 70.61 0.1387 416
Sycamore 37/3.23 303.2 22.61 835.2 89.4 0.1095 480
Upas 37/3.53 362.1 24.71 997.5 106.82 0.0917 535
Yew 37/4.06 479 28.42 1319.6 141.31 0.0693 633
Totara 37/4.14 498.1 28.98 1372.1 146.93 0.0666 648
Rubus 61/3.50 586.9 31.5 1622 173.13 0.0567 714
Sorbus 61/3.71 659.4 33.39 1822.5 194.53 0.0505 764
Araucaria 61/4.14 821.1 37.26 2269.4 242.24 0.0406 868
Redwood 61/4.56 996.2 41.04 2753.2 293.88 0.0334 970

Get a free quote by e-mail: info@qingzhou-cable.com

AAAC conductor-IEC 61089

Code Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
  mm^2 No.xmm mm kg/km KN Ω/Km A
16 18.4 18.4 5.49 50.4 5.43 1.7896 86
25 28.8 28.8 6.87 78.7 8.49 1.1453 113
40 46 46 8.67 125.9 13.58 0.7158 151
63 72.5 72.5 10.89 198.3 21.39 0.4545 200
100 115 115 13.9 316.3 33.95 0.2877 266
125 144 144 15.5 395.4 42.44 0.2302 305
160 184 184 17.55 506.1 54.32 0.1798 355
200 230 230 19.65 632.7 67.91 0.1439 407
250 288 288 21.95 790.8 84.88 0.1151 466
315 363 363 24.71 998.9 106.95 0.0916 535
400 460 460 27.86 1268.4 135.81 0.0721 618
450 518 518 29.54 1426.9 152.79 0.0641 663
500 575 575 31.15 1585.5 169.76 0.0577 706
560 645 645 33.03 1778.4 190.14 0.0516 755
630 725 725 35.01 2000.7 213.9 0.0458 809
710 817 817 37.17 2254.8 241.07 0.0407 866
800 921 921 39.42 2540.6 271.62 0.0361 928
900* 1036 1036 41.91 2861.1 305.58 0.0321 992
1000* 1151 1151 44.11 3179 339.53 0.0289 1051
1120* 1289 1289 46.75 3560.5 380.27 0.0258 1118
1250* 1439 1439 49.39 3973.7 424.41 0.0231 1185